FANUC Alarm SP51 - Low Voltage DC Link
The FANUC Alarm SP51 - Low Voltage DC Link is most commonly caused by issues with the Power Supply Module (PSM) or insufficient AC input voltage. A failure in the PSM or a missing phase in the AC input often leads to a drop in DC bus voltage, triggering this alarm. The most likely fix involves diagnosing and repairing the PSM or correcting the AC input power supply issues.
FANUC Alarm SP51 - Low Voltage DC Link
Low Voltage DC Link
The DC bus voltage in the Fanuc Alpha spindle drive has dropped below the minimum operating threshold. This is similar to SV3 on the servo drive — the power supply feeding the spindle drive's DC bus is insufficient. The spindle cannot operate at safe levels with low DC bus voltage.
Root Cause Summary
The FANUC Alarm SP51 - Low Voltage DC Link is most commonly caused by issues with the Power Supply Module (PSM) or insufficient AC input voltage. A failure in the PSM or a missing phase in the AC input often leads to a drop in DC bus voltage, triggering this alarm. The most likely fix involves diagnosing and repairing the PSM or correcting the AC input power supply issues.
Causes and Fixes
Check PSM LED Display for Alarms
Inspect the LED display on the PSM for any alarm codes or error indicators. Note down any codes displayed as they will provide specific insight into the PSM issue.
Refer to the FANUC PSM alarm code manual for detailed descriptions of any displayed codes.
Ensure the machine is powered down before accessing the PSM to avoid electrical shock.
Reset PSM if Alarm is Present
If an alarm is displayed, attempt a reset by powering down the machine, waiting 5 minutes, and powering it back up. Observe if the alarm reappears on the PSM display.
A recurring alarm after reset often indicates a hardware fault in the PSM requiring replacement or repair.
Do not repeatedly reset without addressing the root cause as it may worsen the issue.
Test PSM Output Voltage
Using a multimeter set to DC voltage, measure the output voltage at the PSM terminals. Compare the reading to the expected range (280-325VDC for 200V class, 560-650VDC for 400V class).
If the voltage is significantly below spec even with no load, the PSM likely needs professional servicing.
High voltage is present; ensure proper insulation and safety gear while measuring.
Call a technician if:
Prevention
Common Mistakes
Related Alarms
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.