380071

Siemens 380071 - PROFIBUS/PROFINET: No output slot available for basic address (size )

PROFIBUS/PROFINET: No output slot available for basic address (size)

An incorrect logical base address was specified for a digital or analog input. Either no slot has been configured for this base address or the requested area extends beyond the end of the slot. For length =1 it is a digital output, For length =2 it is an analog output Control reaction: Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display.

Safety

  • Only qualified personnel should diagnose and clear control alarms; follow the machine builder's safety procedures and lockout/tagout where hardware work is required.

Common Causes

  • An incorrect logical base address was specified for a digital or analog input.
  • Either no slot has been configured for this base address or the requested area extends beyond the end of the slot.
  • For length =1 it is a digital output, For length =2 it is an analog output

Troubleshooting Steps

  1. 1Enter correct base addresses in the machine data: - For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
  2. 2For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
  3. 3NCK restart If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system manufacturer.
  4. 4Switch control OFF - ON