Siemens SINUMERIK codes
Siemens SINUMERIKServo/AxisIntermediate30-120 minutes

300759

Siemens 300759 - Axis drive generator mode: response voltage > monitoring

Axis drive generator mode: response voltage > monitoring

The value in MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) is greater than MD1630: $MD_LINK_VOLTAGE_MON_THRESHOLD (response threshold for DC link monitoring) Control reaction: NC not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm. Channel not ready.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Common Causes

  • The value in MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) is greater than MD1630: $MD_LINK_VOLTAGE_MON_THRESHOLD (response threshold for DC link monitoring)

Troubleshooting Steps

  1. 1Please inform the authorized personnel/service department.
  2. 2Modify drive machine data - Modify MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) or - Modify MD 1630: $MD_LINK_VOLTAGE_MON_THRESHOLD (response threshold for DC link monitoring).
  3. 3Clear alarm with the RESET key in all channels. Restart part program

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.