300744

Siemens 300744 - Axis drive safety monitoring checksum invalid, confirmation and

Axis drive safety monitoring checksum invalid, confirmation and

The actual checksum of the safety-relevant MDs calculated by the drive and stored in MD 1398: $MD_SAFE_ACT_CHECKSUM (display of the checksum of the machine data for safe functions) has another value than the setpoint checksum stored during the last machine acceptance in MD 1399: $MD_SAFE_DES_CHECKSUM (checksum of the machine data for safe functions). The safetyrelevant data have been modified or there is an error. Request: During boot-up of the control Control reaction: Mode group not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.

Root Cause Summary

Alarm 300744 indicates a mismatch between the actual safety-relevant machine data checksum (MD 1398: $MD_SAFE_ACT_CHECKSUM) calculated by the drive and the reference checksum (MD 1399: $MD_SAFE_DES_CHECKSUM) stored during last machine acceptance. This safety monitoring mechanism detects unauthorized or corrupted modifications to safety-critical parameters in the SINUMERIK 840D control system.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Causes and Fixes

  1. 1

    Access Diagnostics > Machine Data on the control panel or use SINUMERIK Operate HMI. Navigate to MDs 1398 and 1399 to compare actual vs. desired checksums.

    Do not modify these checksums directly; they are read-only safety parameters.

  2. 2

    Review recent changes to safety-relevant MDs (e.g., MD 30402: SLS_LIMIT, MD 30406: SSL_LIMIT, MD 32010-32019 for axis safety). Check audit logs or machine history if available.

  3. 3

    Restore the safe machine data to the last known good backup and perform machine acceptance (Commissioning > Safety > Accept Changes) to regenerate MD 1399 checksum.

    Only authorized commissioning personnel should perform acceptance; this typically requires Siemens commissioning software or 840D engineering mode.

  4. 4

    Power-cycle the drive or issue a POWER ON reset via NCK control to reinitialize safety monitoring and verify checksum alignment.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.