300611

Siemens 300611 - Clear alarm with the RESET key in all channels of this mode group. Restart part program.

Clear alarm with the RESET key in all channels of this mode group. Restart part program.

During the measurement, the motor has turned by more than the permissible value entered in MD1020: $MD_MAX_TURN_ROTORPOS_IDENT (maximum rotation of the rotor position identification). The rotation can be caused by switching on a rotating motor or by the identification itself. The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready) Control reaction: Mode group not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm. Channel not ready.

Safety

  • Only qualified personnel should diagnose and clear control alarms; follow the machine builder's safety procedures and lockout/tagout where hardware work is required.

Common Causes

  • During the measurement, the motor has turned by more than the permissible value entered in MD1020: $MD_MAX_TURN_ROTORPOS_IDENT (maximum rotation of the rotor position identification).
  • The rotation can be caused by switching on a rotating motor or by the identification itself.
  • The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready)

Troubleshooting Steps

  1. 1Please inform the authorized personnel/service department.
  2. 2If the rotation was caused by the identification itself, and if the error occurs repeatedly, then reduce MD1019: $MD_CURRENT_ROTORPOS_IDENT (rotor position identification current) or increase MD1020: $MD_MAX_TURN_ROTORPOS_IDENT (maximum rotation of the rotor position identification).
  3. 3Rotor position identification with inductance: stall the motor during the identification - Rotor position identification with movement: check the factor load mass/load moment of inertia MD1076: $MD_FACTOR_MASS / $MD_FACTOR_INERTIA and increase if necessary.
  4. 4Clear alarm with the RESET key in all channels of this mode group. Restart part program