Siemens 840D 27204 - PROFIsafe: double assignment MD - MD
Alarm 27204 fires when a single input assignment ($A_INSE) is configured in multiple locations simultaneously on the 840D control, violating the exclusive assignment rule required by PROFIsafe safety protocol. This double assignment creates configuration conflicts between DMP hardware assignments and PROFIsafe module declarations.
Siemens 840D 27204 - PROFIsafe: double assignment MD - MD
PROFIsafe: double assignment MD - MD
Siemens SINUMERIK alarm 27204: PROFIsafe: double assignment MD [] - MD []. This alarm indicates a fault or error condition on the SINUMERIK 840D control. Refer to the Siemens SINUMERIK alarm documentation for the complete description and remedy.
Root Cause Summary
Alarm 27204 fires when a single input assignment ($A_INSE) is configured in multiple locations simultaneously on the 840D control, violating the exclusive assignment rule required by PROFIsafe safety protocol. This double assignment creates configuration conflicts between DMP hardware assignments and PROFIsafe module declarations.
Safety
Causes and Fixes
Navigate to Diagnostics > Machine Data > $MN_SAFE_IN_HW_ASSIGN in HMI and document all parameterized $A_INSE entries and their index positions.
Cross-reference each $A_INSE entry against MD $MN_PROFISAFE_IN_ASSIGN in the Safety PLC configuration to identify redundant assignments.
The alarm message parameters %1[%2] and %3[%4] indicate the conflicting MD numbers and indices—note these for reconciliation.
Remove the duplicate $A_INSE assignment from either DMP or PROFIsafe configuration, but NOT both. Typically, retain assignment in PROFIsafe module only for safety-critical inputs.
Reload all Safety PLC code (F5 in STEP 7 Safety), re-download to the 840D, and verify alarm clears on next system startup.