Siemens 26102 - Axis drive sign of life missing

Axis drive sign of life missing

For PROFIdrive only: The sign-of-life cell is no longer being updated by the drive Control reaction: Mode group not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Axes of this channel must be re-referenced. Interface signals are set. Alarm display. NC Stop on alarm.

Root Cause Summary

Alarm 26102 indicates the NCK has lost cyclic communication with the specified axis drive module—the sign-of-life telegram is no longer being refreshed within the expected cycle time. This is a critical servo/spindle communication fault that prevents axis motion and requires immediate hardware or parameter verification.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Causes and Fixes

  1. 1

    Power down the machine and inspect all DRIVE-CLiQ connectors (M23 or M12) on axis %2. Check for corrosion, bent pins, and secure seating.

    Verify machine is de-energized before contact inspection.

  2. 2

    In Siemens HMI Diagnostics menu, navigate to [Drives] > [Drive Status] and confirm drive %2 appears with valid status bit. If 'Not Present' is shown, reseat all connectors and reboot.

  3. 3

    If intermittent, replace the DRIVE-CLiQ cable. Log serial number of affected drive and test with a known-good cable to isolate the fault.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.