Okuma OSP Alarm B 2135 - MCS DD encoder link error

MCS DD encoder link error

The MCS detected a communication failure on the DD (direct drive) encoder link for the axis or spindle named in the object field. Position feedback from that encoder is unreliable, so the control stops the axis. This alarm applies only to ICB-H systems.

Common Causes

  • Faulty DD encoder (or its slave sensor) on the indicated axis
  • Damaged encoder link cable or loose/corroded connector
  • Noise or wiring fault causing CRC, parity, or time-out errors on the link
  • Defective inverter unit control board

Troubleshooting Steps

  1. 1Read the code number shown with the alarm: code YY=00 = Error detected at the DD encoder; code YY=01 = Error detected at the DD encoder slave sensor; code ZZZZ bit13 = Communication error with the DD encoder slave sensor; code ZZZZ bit12 = Communication error with the DD encoder; code ZZZZ bit11 = MT buffer error; code ZZZZ bit10 = Transmission loop error in AT mode; code ZZZZ bit9 = Data-over error in the interface receiving section; code ZZZZ bit6 = Modulation code error
  2. 2Note the object (axis name or spindle) and the full code. YY=00 means the error was detected at the DD encoder itself; YY=01 points to the slave sensor.
  3. 3Decode the ZZZZ status bits to identify the failure type: bit0 time-out or bit1 parity suggests cable/connector trouble; bit12/bit13 indicate lost communication with the encoder or slave sensor; bit5 CRC and bit4 format errors point to noise or a failing encoder.
  4. 4Lock out the machine power, then inspect the encoder link cable and connectors on the flagged axis for bent pins, oil contamination, chafing, or loose seating; reseat and clean them.
  5. 5Check cable routing for damage near moving parts and verify shielding/grounding is intact to rule out noise.
  6. 6If the link error persists, substitute or test the DD encoder (or slave sensor if YY=01) on that axis.
  7. 7If the encoder and cabling check out, the inverter unit control board is the remaining suspect; record the alarm number, code, and object and contact Okuma service before replacing it.