HEIDENHAIN 239-02F3 - 2F3 UM-FSUC: deactivation of drive failed CC
The TNC control issued a deactivation command via the UM-FSUC safety protocol but did not receive proper acknowledgment from the inverter module within the expected timeout period. This indicates either a breakdown in the safety-rated communication path between control and drive, or a hardware fault in the UM module preventing it from executing or confirming the deactivation.
HEIDENHAIN 239-02F3 - 2F3 UM-FSUC: deactivation of drive failed CC
2F3 UM-FSUC: deactivation of drive failed CC
The drive could not be deactivated because it is not in a safe state. Safety conditions are not met for shutdown.
Root Cause Summary
The TNC control issued a deactivation command via the UM-FSUC safety protocol but did not receive proper acknowledgment from the inverter module within the expected timeout period. This indicates either a breakdown in the safety-rated communication path between control and drive, or a hardware fault in the UM module preventing it from executing or confirming the deactivation.
Safety
Causes and Fixes
Check physical cable connections
Inspect X116/X126 encoder/drive interface connectors on NCK board. Check cable routing for pinching, excessive bending near connectors, or proximity to power cables causing EMI interference on DRIVE-CLiQ/EnDat signals.
Disconnect control power before inspecting cable connections to prevent accidental ground faults.
Monitor communication diagnostics
Navigate to PLC>Diagnostics>Communication and monitor real-time telegram statistics for the affected CC channel. Look for CRC errors, telegram dropouts, or increased latency values during drive enable/disable cycles.
If error counters increment only during deactivation (not activation), suspect noise coupling during power stage switching - check shield grounding at both ends.
Test with reduced bus load
Temporarily disconnect non-critical devices from the DRIVE bus (additional encoders, I/O modules) to isolate whether bus overload is preventing timely FSUC response. Re-enable one at a time to identify problematic device.
UM-FSUC telegrams have priority, but excessive bus traffic can cause jitter in timing-critical deactivation sequences on older UM firmware versions.
Call a technician if:
Prevention
Common Mistakes
Related Alarms
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?