HEIDENHAIN 23A-0019 - Error in communication with device
This alarm is triggered when the TNC control detects a timeout or protocol error in the cyclic communication exchange with a networked peripheral device. The communication stack in the PLC module monitors data exchange cycles, and when a configured device fails to respond within the expected timeframe, the control raises this alarm identifying the specific device. The root cause is typically physical layer (cabling/power) or network configuration issues rather than control hardware failure.
HEIDENHAIN 23A-0019 - Error in communication with device
Error in communication with device
This TNC7/TNC 640 error indicates a communication failure with a connected device. Inverter (HFL): an error occurred at the interface the affected component ID number: the device, serial number: the unit The control cannot establish or maintain prope
Root Cause Summary
This alarm is triggered when the TNC control detects a timeout or protocol error in the cyclic communication exchange with a networked peripheral device. The communication stack in the PLC module monitors data exchange cycles, and when a configured device fails to respond within the expected timeframe, the control raises this alarm identifying the specific device. The root cause is typically physical layer (cabling/power) or network configuration issues rather than control hardware failure.
Safety
Causes and Fixes
Identify affected device
Note the device name or number shown in the %2 parameter of the alarm. Cross-reference this with the machine's network topology diagram or MOD > System Configuration > Device List to locate the physical device.
The %2 parameter typically shows the device name as configured in the PLC program (e.g., 'Spindle_Drive', 'Tool_Magazine', 'MPG_Panel').
Inspect physical connections
Check all cable connections between the TNC control's PLC module (typically X115 for ProfiNet) through any network switches to the affected device. Verify M12 and RJ45 connectors are fully seated and locking mechanisms engaged.
Power down peripheral devices before disconnecting/reconnecting network cables to prevent backplane damage.
Verify cable continuity
Use a network cable tester or multimeter to verify continuity on all twisted pairs. For ProfiNet, confirm proper shielding continuity. Check for cable damage especially near cable carriers or moving machine components.
Heidenhain recommends Cat5e minimum for ProfiNet; Cat6 or industrial M12 X-coded cables for machine tool environments with high EMI.
Check LED indicators
Observe the LED status on the TNC PLC module X115/X116 connector area and on the affected device's communication port. Green typically indicates link OK, flickering shows data activity, red/amber indicates fault. No LED activity confirms physical layer failure.
On TNC 640 controls, the PLC module LEDs are visible through the front panel access window without opening the cabinet.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.