HEIDENHAIN 236-A204 - ProfiNet: Drive does not react
The TNC control has detected that a configured ProfiNet drive node is not responding within the expected cyclic communication window. This is specifically a ProfiNet fieldbus communication failure between the control and an inverter module, not an internal drive fault, though hardware faults can trigger communication loss.
HEIDENHAIN 236-A204 - ProfiNet: Drive does not react
ProfiNet: Drive does not react
This TNC7/TNC 640 system error indicates The drive does not react. Possible causes. The control has detected an abnormal state that requires attention.
Root Cause Summary
The TNC control has detected that a configured ProfiNet drive node is not responding within the expected cyclic communication window. This is specifically a ProfiNet fieldbus communication failure between the control and an inverter module, not an internal drive fault, though hardware faults can trigger communication loss.
Safety
Causes and Fixes
Identify Affected Drive
Note the drive number %1 from alarm display. Cross-reference in MOD > Machine Configuration > Axis Assignment to determine which physical axis and inverter module corresponds to this number.
Drive numbering starts at 0 for X-axis. On multi-UMC systems, note which cabinet and module position matches the alarm number.
Inspect ProfiNet Cable Integrity
Physically trace the green ProfiNet cable from TNC PL6xxx communication board to the affected UEC/UMC inverter. Check for kinks, cuts, or loose M12/RJ45 connections at both ends. Verify cable click-lock engagement.
Do not disconnect ProfiNet cables while control is powered on - this may cause additional alarms or configuration loss.
Verify ProfiNet Topology
Access MOD > Device Management > ProfiNet and check network topology diagram. Affected drive will show red icon or 'No Response' status. Verify daisy-chain sequence matches physical installation.
ProfiNet requires proper line termination. Last device in chain must have termination resistor active or termination plug installed.
Test Cable with Known Good
If available, temporarily swap the ProfiNet cable with a known working segment. Use only industrial ProfiNet-certified cables (CAT5e minimum, shielded). Standard Ethernet patch cables may cause intermittent failures.
Heidenhain recommends max 10m cable length between ProfiNet nodes. Longer distances require ProfiNet switches with IRT capability.
Call a technician if:
Prevention
Common Mistakes