HEIDENHAIN 231-C008 - C008 I-CTRL communication: QUEUE
HEIDENHAIN alarm 231-C008 indicates a communication queue overflow or timeout between the speed controller and current controller within the drive system. This typically occurs when the internal communication buffer becomes saturated or when there's a timing mismatch in the control loop data exchange.
HEIDENHAIN 231-C008 - C008 I-CTRL communication: QUEUE
C008 I-CTRL communication: QUEUE
This TNC 640 error indicates a communication failure between control components. The HSCI data exchange has been interrupted or corrupted.
Root Cause Summary
HEIDENHAIN alarm 231-C008 indicates a communication queue overflow or timeout between the speed controller and current controller within the drive system. This typically occurs when the internal communication buffer becomes saturated or when there's a timing mismatch in the control loop data exchange.
Safety
Causes and Fixes
Access Drive Parameters
Navigate to MOD function → Machine Parameters → Drive Parameters (MP7210-MP7299) to check current controller settings.
Always backup current parameters before making changes using the parameter export function.
Verify Communication Timing
Check MP7220 (Current controller cycle time) and MP7221 (Speed controller cycle time) for proper ratio - typically 1:4 or 1:8.
Incorrect timing ratios can cause permanent drive damage.
Reset Communication Queue
Set MP7230 (Communication reset) to 1, cycle power, then reset to 0 to clear internal buffers.
Monitor the drive LED status during reset - should show green within 10 seconds.
Validate Settings
Run axis reference movement and monitor for alarm recurrence while checking drive diagnostics in Test Run mode.
Call a technician if:
Prevention
Common Mistakes