HEIDENHAIN 231-A001 - A001 Cancelation of brake-test call monitoring
HEIDENHAIN alarm 231-A001 occurs when the automatic brake test sequence is interrupted or cannot complete properly. This typically happens when safety doors are opened during the brake test or when drive enable signals are lost during the monitoring phase.
HEIDENHAIN 231-A001 - A001 Cancelation of brake-test call monitoring
A001 Cancelation of brake-test call monitoring
This TNC 640 error relates to the motor brake system. The control has detected an issue with brake operation or testing.
Root Cause Summary
HEIDENHAIN alarm 231-A001 occurs when the automatic brake test sequence is interrupted or cannot complete properly. This typically happens when safety doors are opened during the brake test or when drive enable signals are lost during the monitoring phase.
Safety
Causes and Fixes
Check door status indicators
Navigate to MOD > Machine Parameters > Safety and verify all door status signals show closed (typically parameters 128200-128207).
Never bypass safety door switches during brake testing
Verify door switch functionality
Test each protective door switch by opening/closing doors while monitoring PLC inputs in the diagnostic screen.
Use PLC > Inputs/Outputs to monitor door switch states in real-time
Restart brake test sequence
Ensure all doors are properly closed, then restart the brake test from Setup > Spindle/Axis > Brake Test menu.
Wait for all door status LEDs to show green before initiating test
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?