HEIDENHAIN 230-04E6 - Incorrect UVR/UEC configuration: config. duplicated:

Incorrect UVR/UEC configuration: config. duplicated:

The hsciUvIndex parameter is duplicated across CfgSupplyModule3xx instances. Each instance must have a unique value.

Root Cause Summary

HEIDENHAIN alarm 230-04E6 occurs when multiple CfgSupplyModule3xx instances have identical hsciUvIndex parameter values in the machine configuration. This creates a conflict in the UVR/UEC communication system as each supply module must have a unique index identifier.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Access machine parameter configuration

    Navigate to MOD function → Machine Parameters → Communication → UVR Configuration to view CfgSupplyModule settings.

    Use the search function in machine parameters to quickly locate CfgSupplyModule entries

  2. 2

    Identify conflicting hsciUvIndex values

    Check all CfgSupplyModule3xx instances and note which ones have identical hsciUvIndex parameter values as indicated in the alarm message %1 and %2.

    Document current settings before making changes

  3. 3

    Assign unique hsciUvIndex values

    Modify the hsciUvIndex parameter in conflicting CfgSupplyModule instances to ensure each has a unique value (typically sequential: 0, 1, 2, etc.).

    Follow the physical connection order when assigning index numbers for easier troubleshooting

  4. 4

    Save configuration and restart

    Save the machine parameters and perform a complete control restart to apply the new UVR configuration.

    Ensure all axes are in safe position before restarting the control

DIY Feasiblehigh confidence

Call a technician if:

  • ·Parameter corruption persists after reset
  • ·Physical UVR hardware issues discovered
  • ·Multiple related communication alarms appear

Prevention

  • Always document UVR configuration before making changes
  • Verify parameter backups before importing configurations
  • Use systematic hsciUvIndex numbering scheme

Common Mistakes

  • Importing configuration files without checking compatibility
  • Not verifying physical hardware layout before parameter changes
  • Forgetting to restart control after parameter modifications