HEIDENHAIN 230-0474 - Inputs for axis group enabling have multiple definitions
HEIDENHAIN alarm 230-0474 occurs when axis group enabling inputs are defined in both the IOC configuration file and the machine parameters simultaneously. The TNC control detects this conflict during system initialization, with the configuration data taking priority over IOC definitions.
HEIDENHAIN 230-0474 - Inputs for axis group enabling have multiple definitions
Inputs for axis group enabling have multiple definitions
Axis-group enabling inputs are defined in both IOC file and configuration data. Configuration entries have priority.
Root Cause Summary
HEIDENHAIN alarm 230-0474 occurs when axis group enabling inputs are defined in both the IOC configuration file and the machine parameters simultaneously. The TNC control detects this conflict during system initialization, with the configuration data taking priority over IOC definitions.
Safety
Causes and Fixes
Access machine parameter menu
Press MOD key, select 'Machine Parameters', navigate to MP7500 series (Axis Group Parameters) to check for axis group enable definitions.
Use the search function in machine parameters by entering '7500' to quickly locate axis group parameters.
Review IOC configuration file
Access the IOC file through TNCopt or file manager, search for axis group enable signal definitions in the digital input assignments section.
Always backup the IOC file before making any modifications.
Remove duplicate definitions
Delete either the IOC file entries or clear the corresponding machine parameters MP7500.x, keeping only one definition method active.
Machine parameter definitions take priority, so if both exist, the IOC entries are ignored but still trigger the alarm.
Perform control restart
Execute a complete TNC restart to reload the configuration and verify alarm clearance.
Ensure all programs are saved before restarting the control.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.