Siemens SINUMERIK Controller
Parameter · Intermediate · 30-120 minutes
Siemens 4270 - Machine data assigns not activated NCK input/output byte
Alarm 4270 fires when machine data (MD) assigns a digital or analog I/O signal to an NC function, but the corresponding NCK input/output processing has not been activated via the enable parameter. This typically occurs when MD parameters reference I/O bytes without setting the associated activation flags in the NCK configuration.
Siemens 4270 - Machine data assigns not activated NCK input/output byte
Machine data assigns not activated NCK input/output byte
The specified machine data assigns a digital input/output byte or an analog input/output signal the processing of which has not been activated to an NC function Control reaction: NC not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.
Root Cause Summary
Alarm 4270 fires when machine data (MD) assigns a digital or analog I/O signal to an NC function, but the corresponding NCK input/output processing has not been activated via the enable parameter. This typically occurs when MD parameters reference I/O bytes without setting the associated activation flags in the NCK configuration.
Safety
Causes and Fixes
Navigate to Diagnostics > Machine Data (MD) menu and identify the problematic MD parameter number from alarm text %1. Cross-reference the I/O byte number %2 in the alarm message.
Locate the corresponding NCK activation/enable machine data parameter. For example, if MD10060 assigns spindle enable to byte 4, verify MD10010 (NCK spindle enable flag) is set to 1 or the appropriate activation value per SINUMERIK documentation.
Check MD parameter family: MD10xxx (spindle), MD11xxx (axis), MD14xxx (digital I/O), MD15xxx (analog I/O) for activation flags.
Set the NCK activation flag to the correct value (typically 1 or non-zero). Save machine data and perform a warm restart (NC Start button or Ctrl+Shift+R in MDI mode) to reload NCK configuration.
Verify the I/O byte assignment is valid (0-127 for digital, 0-255 for analog) and does not conflict with other MD assignments in the same range.
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.