Siemens 301711 - Axis drive transmission length SSI motor measuring system
Alarm 301711 indicates a configuration mismatch between the SSI encoder's transmission length (MD 1028) and the total number of bits required by the motor measuring system parameters. The SSI transmission length is insufficient to accommodate all parameterized bits for multiturn (MD 1021), singleturn resolution (MD 1022), and status bits (MD 1027), causing the safety-critical encoder data to be incomplete or corrupted.
Siemens 301711 - Axis drive transmission length SSI motor measuring system
Axis drive transmission length SSI motor measuring system
The configuration of the motor measuring system for an SSI encoder is incorrect: MD 1028 $MD_NO_TRANSMISSION_BITS (SSI transmission length) is less than the number of all parameterized bits in MD 1021 $MD_ENC_ABS_TURNS_MOTOR (multiturn), MD 1022 $MD_ENC_ABS_RESOL_MOTOR (singleturn) and MD 1027 $MD_ENC_CONFIG bit 14 (alarm bit) and MD 1027 $MD_ENC_CONFIG bit 12 (parity bit) Control reaction: Mode group not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.
Root Cause Summary
Alarm 301711 indicates a configuration mismatch between the SSI encoder's transmission length (MD 1028) and the total number of bits required by the motor measuring system parameters. The SSI transmission length is insufficient to accommodate all parameterized bits for multiturn (MD 1021), singleturn resolution (MD 1022), and status bits (MD 1027), causing the safety-critical encoder data to be incomplete or corrupted.
Safety
Causes and Fixes
Access Diagnostics > Parameters > Motor Data (MD) for the affected axis/drive. Navigate to MD 1028 and note the current SSI transmission length value.
Calculate required transmission bits: (MD 1021 multiturn bits) + (MD 1022 singleturn bits) + (MD 1027 status bits). Document this total.
Ensure MD 1022 is the actual resolution in bits, not the decimal resolution value.
If MD 1028 is less than the calculated total, increase MD 1028 to match or exceed the required bit count. Consult the SSI encoder datasheet for maximum supported transmission length.
Do not arbitrarily increase MD 1028 beyond the encoder's hardware capability; this will cause transmission errors.
Save parameters (MD), perform a SINUMERIK cold restart (Power ON/OFF cycle), and verify alarm 301711 clears during NCK initialization.
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.