Siemens SINUMERIK Controller
Communication · Intermediate · 30-120 minutes
Siemens 28012 - NCU link: synchronization cycle signal failure times
Alarm 28012 indicates the NCU-link synchronization clock line has failed to deliver cycle signals to NCU slave modules, breaking the real-time handshake required for multi-axis coordination. This typically stems from hardware communication failures, timing parameter misconfigurations, or corruption in the NCU-link interface that prevents proper cycle synchronization between NCU 1 (master) and subordinate NCUs.
Siemens 28012 - NCU link: synchronization cycle signal failure times
NCU link: synchronization cycle signal failure times
Error message of the NCU link module that does not occur at NCU 1. The NCU's are synchronized via their own NCU- link clock line. A large number of cycle signals are missing. The parameter indicates how many cycles have failed Control reaction: NC not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.
Root Cause Summary
Alarm 28012 indicates the NCU-link synchronization clock line has failed to deliver cycle signals to NCU slave modules, breaking the real-time handshake required for multi-axis coordination. This typically stems from hardware communication failures, timing parameter misconfigurations, or corruption in the NCU-link interface that prevents proper cycle synchronization between NCU 1 (master) and subordinate NCUs.
Safety
Causes and Fixes
Power down the machine and visually inspect all NCU-link cables for bent pins, corrosion, loose connectors, or visible damage. Reseat both ends of the NCU-link connector firmly until you hear a click.
Ensure the control system is in OFF mode and all axes are safe before opening control cabinet.
Use an oscilloscope to measure the synchronization clock line signal amplitude and frequency at the slave NCU connector. Verify the signal maintains 5V digital levels and the cycle frequency matches the setting in MD 20080 (NCU_LINK_CYCLE_TIME).
If signal is degraded, replace the NCU-link cable with a Siemens-certified shielded twisted-pair cable (typically 6FX series). Ensure cable length does not exceed 20 meters and shield is grounded at both ends.
Power cycle the control system and monitor alarm 28012 counter in Diagnostics > Machine > NCU-Link Status menu. If counter increments slowly or stops, hardware issue is resolved.
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.