Siemens SINUMERIK codes
Siemens SINUMERIKSafetyIntermediate30-120 minutes

20106

Siemens 840D 20106 - Emergency stop set by the digitizer

Emergency stop set by the digitizer

Siemens SINUMERIK 840D alarm 20106 indicates that an emergency stop was triggered by the digitizer (3D probe or digitizing system). The digitizing system has activated the emergency stop circuit.

Root Cause Summary

Alarm 20106 indicates the digitizing unit (probe/touch trigger sensor) has detected a critical fault condition and autonomously triggered an emergency stop via the NCK safety circuit. This typically involves hardware malfunction, signal integrity loss, or unsafe probe state detection that prevents continued axis motion.

Safety

  • Refer to Siemens documentation
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Verify physical probe connection at the probe head and control cabinet terminal block. Check MD 37000 (ProbeType) and MD 37010 (ProbeTouchSignalType) match the installed probe model in Diagnostics > Measuring Probe menu.

    Do NOT bypass safety interlocks. Confirm E-stop is active before servicing probe hardware.

  2. 2

    Test probe signal in NCK diagnostics: Navigate to Diagnostics > Inputs/Outputs > Probe Input (typically DI port assigned in MD 37100). Trigger probe mechanically and verify signal state change from 0 to 1 (or inverted logic per MD 37020).

  3. 3

    If signal does not respond, measure continuity and voltage at probe connector using multimeter. Expected: 24V logic signal with <100ms response time. Check harness for pinch damage or moisture ingress.

  4. 4

    Replace probe or harness assembly and re-initialize probe calibration via Diagnostics > Measuring Probe > Calibration. Clear alarm with soft reset (MDI: RESET) or hard reset if required.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.