Siemens 840D 101133 - MDx120 CURRCTRL_GAIN could not be calculated
Alarm 101133 indicates the CNC system cannot calculate the current controller gain (CURRCTRL_GAIN) parameter during automatic servo optimization or commissioning. This typically occurs when essential motor or drive parameters in MD1120 series are missing, incorrect, or inconsistent, preventing the control loop from being properly tuned.
Siemens 840D 101133 - MDx120 CURRCTRL_GAIN could not be calculated
MDx120 CURRCTRL_GAIN could not be calculated
Siemens SINUMERIK operator message 101133: MDx120 CURRCTRL_GAIN could not be calculated. This is an informational message from the SINUMERIK control indicating a system status or operation result that may require operator action.
Root Cause Summary
Alarm 101133 indicates the CNC system cannot calculate the current controller gain (CURRCTRL_GAIN) parameter during automatic servo optimization or commissioning. This typically occurs when essential motor or drive parameters in MD1120 series are missing, incorrect, or inconsistent, preventing the control loop from being properly tuned.
Safety
Causes and Fixes
Access drive commissioning menu and verify MD1121 (rated motor current), MD1125 (stator resistance), and MD1130 (motor inductance) are populated with nameplate values.
Compare entered motor parameters against motor nameplate data and manufacturer specifications. Correct any discrepancies.
If motor data is unavailable, perform motor data identification routine via drive parameter p1900=1 (SINAMICS) or equivalent automatic identification.
Ensure motor shaft is mechanically decoupled during identification to prevent unexpected motion
Reset alarm with NC START and attempt servo optimization again. Verify CURRCTRL_GAIN is now calculated and displayed in MD1120.