KUKA Robot codes
KUKA RobotSystemBasic

KRC0896

KUKA Robot KRC0896 - RIGHT OPERAND NOT EQUAL TO INT, CHAR 2232

RIGHT OPERAND NOT EQUAL TO INT, CHAR 2232

This alarm indicates a type mismatch during runtime where the right operand in an expression at character position 2232 is not of integer (INT) or character (CHAR) type as expected. The KRL compiler/interpreter encountered an incompatible data type when evaluating an operation that requires INT or CHAR operands.

Common Causes

  • Right operand is REAL, BOOL, or other incompatible type instead of INT/CHAR
  • Incorrect variable declaration or assignment that changed expected data type
  • Missing type conversion function (e.g., INT(), CHAR()) for the right operand
  • Function return type does not match INT/CHAR requirement
  • Array or structure element accessed with wrong data type

Troubleshooting Steps

  1. 1Locate line 2232 in the KRL source file and identify the expression causing the alarm
  2. 2Verify the data type of the right operand variable or expression in that operation
  3. 3Check variable declarations to ensure correct types are assigned (INT or CHAR expected)
  4. 4Add explicit type conversion functions if needed (e.g., INT(variable) or CHAR(variable))
  5. 5Review function calls at character 2232 to confirm return types match INT/CHAR requirements
  6. 6Recompile the KRL program after corrections and test the syntax

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.