Heidenhain codes
HeidenhainSafetyIntermediate30-120 minutes

330-008B

HEIDENHAIN 330-008B - CC inverter for axes RDY=1 (safety relay)

CC inverter for axes RDY=1 (safety relay)

The power module is reporting ready status when it should be switched off. This indicates a potential fault in the safety control circuit.

Root Cause Summary

This alarm indicates the inverter's safety relay monitoring circuit has detected an unsafe condition where the RDY (ready) signal is active when the drive should be in a disabled state. This typically results from stuck safety relay contacts, faulty enable signal wiring, or a malfunctioning CC inverter module power card that has lost proper control of its safety circuit. The TNC control generates this fault to prevent unintended axis motion from a drive that shows ready status outside of normal enable conditions.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Verify Safety Circuit State

    With machine in emergency stop, access MOD 9 (Service Mode) and navigate to 'Drive Diagnostics' or 'CC Status Monitor'. Check the RDY signal status for the affected axis - it should show RDY=0 when E-stop is active. If it shows RDY=1, the safety relay is stuck.

    Do not attempt to release emergency stop if RDY signal shows active during E-stop condition - this indicates a safety system failure.

  2. 2

    Measure Relay Contact Continuity

    Power down the complete control system and disconnect axis motor power cables. Remove the X112 connector from the affected CC module. Use a multimeter to check continuity across the safety relay output pins (typically pins 1-2 for K1 and 3-4 for K2 on X112). Stuck relays will show <1 ohm resistance when they should be open circuit.

    If you hear the relay clicking during power-up but contacts remain closed, the relay coil works but contacts are welded - this confirms relay replacement is needed.

    Ensure all power is isolated and capacitors discharged (wait 5 minutes) before touching any CC module connections.

  3. 3

    Replace CC Inverter Module

    If stuck relay is confirmed, the CC inverter module power card must be replaced. Document the axis assignment and all parameter settings from the System Parameters (MOD function, System Settings). Replace the complete CC module with a spare, ensuring correct axis assignment in CfgAxisEnable parameters.

    After replacement, perform a full drive commissioning including encoder reference marks and axis testing before returning to production.

Service Recommendedmedium confidence

Call a technician if:

  • ·Safety system modifications required
  • ·Inverter parameter changes needed
  • ·Electrical measurements show unexpected values

Prevention

  • Regular safety system testing per maintenance schedule
  • Keep X72 connectors clean and properly seated
  • Monitor K1 relay operation during routine diagnostics

Common Mistakes

  • Bypassing safety relays during troubleshooting
  • Changing STO parameters without proper documentation
  • Ignoring related alarms that may indicate root cause