HEIDENHAIN 239-001C - 1C CC-FSUC: voltage monitoring impaired CC
HEIDENHAIN alarm 239-001C indicates the FS (Functional Safety) microcontroller has detected a fault in voltage monitoring circuits on CC axis card %2. This typically occurs when supply voltages fall outside acceptable tolerances or monitoring circuits fail, compromising the safety system's ability to detect power-related faults.
HEIDENHAIN 239-001C - 1C CC-FSUC: voltage monitoring impaired CC
1C CC-FSUC: voltage monitoring impaired CC
This safety-related error indicates a fault in the FS microcontroller. The FS microcontroller reports defective monitoring of the voltage. The control has detected a safety issue that may affect safe operation.
Root Cause Summary
HEIDENHAIN alarm 239-001C indicates the FS (Functional Safety) microcontroller has detected a fault in voltage monitoring circuits on CC axis card %2. This typically occurs when supply voltages fall outside acceptable tolerances or monitoring circuits fail, compromising the safety system's ability to detect power-related faults.
Safety
Causes and Fixes
Check CC card supply voltages
Navigate to MOD > Service > Diagnosis > Voltage monitoring and verify all supply voltages on the affected CC card are within specification (+24V ±5%, ±15V ±5%).
Use the TNC's built-in voltage display rather than external meters for initial diagnosis as it shows what the FS controller actually sees.
Inspect power supply connections
Power down and check all connector contacts on X101 (24V supply) and X102 (±15V supply) on the CC card for corrosion, looseness, or damage.
Always follow LOTO procedures and wait 5 minutes after power-down before handling connections.
Measure external supply stability
Using a DMM, verify the incoming 24VDC supply stability under load - voltage should remain within 22.8V to 25.2V during axis movement.
Check supply ripple with oscilloscope - excessive ripple (>200mV p-p) can cause intermittent FS monitoring faults.
Reset FS monitoring system
After correcting voltage issues, perform FS system reset via MOD > Service > FS Reset and cycle power to reinitialize voltage monitoring.
FS reset requires machine parameter MP7300 to be temporarily set to 1 - restore to 0 after reset.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.