Heidenhain Controller
Parameter · Intermediate · 30-120 minutes
HEIDENHAIN 140-0023 - Data type changed with data object Attribute
The root cause is an incompatible data type assignment in the PLC program structure where a variable, table entry, or configuration object has been defined with a different data type than expected by the control's PLC runtime environment. This typically occurs after software updates, manual program modifications, or restoration from backups with mismatched PLC configurations.
HEIDENHAIN 140-0023 - Data type changed with data object Attribute
Data type changed with data object Attribute
The loaded configuration data comes from an older control version. The data type of an attribute was changed by update rules.
Root Cause Summary
The root cause is an incompatible data type assignment in the PLC program structure where a variable, table entry, or configuration object has been defined with a different data type than expected by the control's PLC runtime environment. This typically occurs after software updates, manual program modifications, or restoration from backups with mismatched PLC configurations.
Safety
Causes and Fixes
Identify Changed Data Object
Access MOD mode > PLC > Error Log and note the exact data object '%1' '%2' and attribute '%3' displayed in the alarm. Record these identifiers for reference.
The alarm parameters are displayed in sequence: %1=object type (e.g., M, T, Q), %2=object identifier, %3=specific attribute name
Review PLC Source Code
In Programming mode, open the PLC program file (typically plc.src or machine-specific .PLC file) and search for the identified data object declaration using the TNC's text search function (GOTO > Search).
Look for VAR, VAR_GLOBAL, or TYPE declarations that define the flagged object
Compare with OEM Reference
Obtain the correct PLC program version from the machine tool builder or from your documented backup library and compare the data type definition of the affected object.
Do not modify OEM-protected PLC code without authorization from the machine tool builder
Correct Data Type Definition
Modify the data object declaration to match the required data type (e.g., change from INT to DINT, BOOL to BYTE, etc.) ensuring compatibility with all references throughout the PLC program.
Common data type corrections: marker bits should be BOOL, counters typically DINT, analog values often REAL
Recompile PLC Program
Navigate to MOD > PLC > Compile and execute a complete PLC recompilation. Monitor the compilation output for additional errors or warnings related to the modified object.
Successful compilation will show 'PLC compiled without errors' - any remaining errors must be resolved before proceeding
Call a technician if:
Prevention
Common Mistakes
Related Alarms
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?