Siemens SINUMERIK codes
Siemens SINUMERIKServo/AxisIntermediate30-120 minutes

300724

Siemens 300724 - Axis drive number of pole pairs invalid

Axis drive number of pole pairs invalid

FDD: The configured number of pole pairs in the drive MD 1112: $MD_NUM_POLE_PAIRS is outside the permissible range limits. MSD: Modify MD 1134: $MD_MOTOR_NOMINAL_FREQUENCY (rated motor frequency) or MD 1400: $MD_MOTOR_RATED_SPEED (rated motor speed) is not correct Control reaction: NC not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Common Causes

  • FDD: The configured number of pole pairs in the drive MD 1112: $MD_NUM_POLE_PAIRS is outside the permissible range limits.
  • MSD: Modify MD 1134: $MD_MOTOR_NOMINAL_FREQUENCY (rated motor frequency) or MD 1400: $MD_MOTOR_RATED_SPEED (rated motor speed) is not correct

Troubleshooting Steps

  1. 1Please inform the authorized personnel/service department.
  2. 2For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
  3. 3For third-party motors: Check and, if necessary, refer to the motor data sheet to correct MD 1112: $MD_NUM_POLE_PAIRS (number of motor pole pairs).
  4. 4Switch control OFF - ON. 2-727

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.