Siemens 300502 - Axis drive maximum current monitoring of phase current R

Axis drive maximum current monitoring of phase current R

The phase current R is greater than or equal to 1.05 times the maximum power section current MD 1107: $MD_INVERTER_MAX_CURRENT (transistor limit current) Control reaction: Mode group not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm. Channel not ready.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Common Causes

  • The phase current R is greater than or equal to 1.05 times the maximum power section current MD 1107: $MD_INVERTER_MAX_CURRENT (transistor limit current)

Troubleshooting Steps

  1. 1Please inform the authorized personnel/service department.
  2. 2Check max. power section current in MD 1107 $MD_INVERTER_MAX_CURRENT (transistor limit current) - Check the motor data (motor code) - Motor has ground or winding fault - Check the controller data - Check the power section and motor terminals (including motor protection) - Error in actual current measurement (if necessary, replace 611D power section or controller module)
  3. 3Switch control OFF - ON