HEIDENHAIN 239-01B3 - 1B3 UM-FSUC: cyclic communication overloaded CC
Alarm 239-01B3 indicates the FS (Functional Safety) microcontroller is overwhelmed by excessive cyclic communication telegrams from the TNC control. This typically occurs when the EnDat/1Vpp encoder communication cycle time is too aggressive for the system configuration or when multiple high-resolution encoders are overloading the FS communication bus.
HEIDENHAIN 239-01B3 - 1B3 UM-FSUC: cyclic communication overloaded CC
1B3 UM-FSUC: cyclic communication overloaded CC
This safety-related error indicates a fault in the FS microcontroller. The FS microcontroller has received too many cyclic telegrams. The control has detected a safety issue that may affect safe operation.
Root Cause Summary
Alarm 239-01B3 indicates the FS (Functional Safety) microcontroller is overwhelmed by excessive cyclic communication telegrams from the TNC control. This typically occurs when the EnDat/1Vpp encoder communication cycle time is too aggressive for the system configuration or when multiple high-resolution encoders are overloading the FS communication bus.
Safety
Causes and Fixes
Check current encoder cycle time
Navigate to MOD > Machine Parameters > MP7440 ENDAT_CYCLE_TIME and note the current value. Values below 125μs often cause this alarm with multiple encoders.
Document all encoder types and resolutions before making changes
Increase cycle time incrementally
Increase MP7440 from current value by 25μs increments (e.g., from 100μs to 125μs). Restart control after each change.
Do not exceed 500μs as this may affect positioning accuracy
Test axis movement
Perform reference run on all axes and execute test program with rapid movements to verify alarm clearance and maintained performance.
Monitor FS communication load
Check diagnostic screen PLC > Info > FS Communication to verify telegram load is below 80% after changes.
Call a technician if:
Prevention
Common Mistakes
Related Alarms
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.